Keywords | 12 kW, 18-pulse transformer arrangement, 200 A, 60 V, Bridge circuits, control strategy, DC-DC power converters, DC-link currents balance, Diodes, full-bridge converters, harmonic distortion, isolated high power factor power supply, isolation, power conversion harmonics, power factor correction, Power supplies, power supplies to apparatus, power transformers, Pulse width modulation, Reactive power, Rectifiers, regulated DC output, Telecommunication control, Topology |
Abstract | This work proposes a new isolated high power factor 12 kW power supply based on an 18-pulse transformer arrangement. Three full-bridge converters are used for isolation and to balance the DC-link currents, without current sensing or a current controller. The topology provides a regulated DC output with a very simple control strategy. Simulation and experimental results are presented in this paper |